The YOKOGAWA EY200 Digital Earth Tester
Designed to safety standard IEC 61557
- Reference to IEC 60529: Degrees of protection provided by enclosures (IP54). Measurement can be made even under adverse weather conditions
- Large, easy-to-read LCD digital display
- 2P Test leads (for simplified measurement) has a structure that both the safety alligator clip and the test probe are available
- Warns when earth resistance of auxiliary earth spikes exceeds the permissible limit
- Convenient carrying soft bag for accessories etc.
- 3-Pole Earth Resistance Measurement (Precise Measurement)
Connect the earth/ground electrode (E) and auxiliary spikes (P, C) to the main body using the accessory test lead. Put apart 5 to 10 m between E and P, and P and C, respectively. E, P, and C should be approximately in a line.
YOKOGAWA EY200 Digital Earth Tester Specifications:
NAME | MODEL |
---|---|
DIGITAL EARTH TESTER | EY200 |
DISPLAY | LCD Digital Display: 1999-count digital reading |
MEASURING RANGE | Earth Resistance: 2000Ω LSD: 0.01 to 1ΩEarth Voltage: 200V |
ACCURACY | Earth Resistance:20Ω range: ±2%rdg±0.1Ω 200 Ω range: ±2%rdg±3dgt 2000 Ω range: ±2%rdg3dgt Earth Voltage: ±1%rdg±4dgt |
MEASURING FREQUENCY | Approx. 820Hz |
MEASURING CURRENT | Approx. 3mA (at 20Ω range) |
BATTERY LIFE | Approx. 4.5hours (at 5 second measuring 3300 times) |
OPERATING TEMP. AND HUMIDITY | 0~40°C, 85%Rh or less |
DIMENSIONS | Approx. 105x158x70mm |
WEIGHT | Approx. 550g |
STANDARD ACCESSORIES | 3-pole Test Lead (Model 98074)Earth Spikes (for EY200) (Model 98070) 2-pole Test Lead Set (Model 98075) Soft Case (Model 93041) Shoulder Belt (for EY200) (Model 99018) Six AA (R6) dry cells User’s Manual |
Reviews
There are no reviews yet.