The Kyoritsu 3132A is an analogue insulation tester with three ranges for insulation resistance measurement and two continuity testing (resistance tests) ranges.
The KYORITSU 3132A is designed to safety standards: IEC 61557-1 (General requirements for measuring equipment for low voltage distribution systems) IEC 61557-2 (Equipment for insulation resistance measurement for low voltage distribution systems) IEC 61557-4 (Equipment for resistance tests for low voltage distribution systems) Dust and drip proof construction to IP54
- The Kyoritsu 3132A has always been a popular choice because of its price and simplicity for insulation testing.
- Test Voltage: 250V / 500V / 1000V
- Measuring Range: 100MΩ, 200MΩ, 400MΩ
- Voltage Measuring Range – 0~600V AC
- Resistance Range: 3Ω / 500Ω (1.5Ω / 20Ω Midrange)
- Easy to read scale means no confusing digital readings.
- Zero out your trailing lead resistance so you don’t need to subtract the resistance of your trailing earth lead every time you test.
- •1mA rated test current at the maximum resistance.
- 200mA short circuit current on continuity testing.
- Automatic discharge of circuit capacitance. (any charge stored in the circuit under test will be automatically discharged after testing.)
- Live circuit warning buzzer and neon lamp.
- Small and lightweight. Shock resistant new case material.
- AC voltmeter with linear, easy-to-read scale.
- CAT III 600V
- Runs on 6 x AA batteries
KYORITSU 3132A Specifications:
Insulation Resistance
Test voltage | 250V/500V/1000V |
---|---|
Measuring ranges (Mid-scale value) | 100MΩ/200MΩ/400MΩ (1MΩ) (2MΩ) (4MΩ) |
Output voltage on open circuit | Rated test voltage+20%, -0% |
Nominal current | 1mA DC min. |
Output short circuit current | 1 – 2mA DC |
Accuracy | 0.1 – 10MΩ/0.2 – 20MΩ/0.4 – 40MΩ (Accuracy Guaranteed Ranges) ±5% of indicated value |
Continuity
Measuring ranges (Mid-scale value) | 3Ω/500Ω (1.5Ω) / (20Ω) |
---|---|
Output voltage on open circuit | 4.1V DC approx. |
Measuring current | 210mA DC min. |
Accuracy | ±1.5% of scale length |
AC Voltage
AC Voltage | 0 – 600V AC |
---|---|
Accuracy | ±5% of scale length |
General
Safety Standard | IEC 61010-1 CAT III 600V Pollution Degree 2 IEC 61010-2-031 IEC 61557-1/2/4 |
---|---|
IP Rating | IEC 60529-IP54 |
EMC Standard | IEC 61326-1 |
Power source | R6 (AA) (1.5V) × 6 |
Dimensions | 106(L) × 160(W) × 72(D)mm |
Weight | 560g approx. |
Included Accessories | 7122B (Test leads) Pouch for test leads 8923 (F500mA/600V fuse) × 2 R6 (AA) × 6 9121 (Shoulder Strap) Instruction Manual |