The TnT RCD Portable Appliance Tester boasts a comprehensive list of tests and analysis as required under the AS/NZS 3760:2010 Standards, with 10 amp (TnT RCD) and 20 amp (TnT RCD 20A) current load capacity versions available. Conducting tests is simple with one button test procedures and easy to read results.
With the flexibility of lithium ion battery power, the TnT RCD Appliance Tester gives you greater versatility with your testing than ever before. The internal lithium ion battery comes with safety focused design and more capacity to run the tester for up to 3000 sets of tests on a single charge.
The new TnT RCD design has isolation functionality built in, eliminating the need for bulky external isolation transformers, making RCD tests quicker and easier. The TnT RCD is designed for high power efficiency and faster data processing and also comes with AC/DC power operation.
Designed and manufactured in Australia to meet stringent testing requirements – some of the tighest in the world – TnT RCD now sets its own new standard of reliability and ruggedness, and now features a 24 month conditional warranty.
Specifications
Mains Supply Tests | Checks Polarity and continuity of mains supply by LED indicators (A-N, A-E, and N-E). (Flashing red LED indicates test fail) |
Class I Tests – Earthed Appliance | Appliance Check: Ensures appliance is plugged in and turned on. Earth Bond Test: 200mA test current. Pass level Less than 1.0 Ω. Measurement: 0.01Ω to 10 Ω. Insulation Test: 500VDC / 250VDC. Pass level Greater than 1M Ω. Measurement: 0.1Ω to 10MΩ. *See also Leakage Test |
Class II Tests – Double Insulated Appliance. | Appliance Check: Ensures appliance is plugged in and turned on. Insulation Test: 500VDC / 250VDC. Pass level greater than 1MΩ. Measurement: 0.1Ω to 10MΩ. *See also Leakage Test |
Extension Lead Tests | Leakage Current: 0 to 30.0mA at 200 to 265 Load Current: 0.0 to 10Amp (20Amp for TnT RCD 20A) Voltage: 200 to 265VAC – Power Factor: 0.00 to 1.00 Apparent Power: 0 to 2400VA -Power 0 to 2400W |
Meter Mode® | Green flashing LED denotes Meter Mode is engaged Load Current: 0.0 to 10Amp Voltage: 200 to 265VAC Apparent Power: 0 to 2400VA Power: 0 to 2400W |
RCD Tests | Trip Current: 2 to 500mA in 1mA steps – User selectable. Trip Time: 0 to 3,000ms at .001sec resolution. Current Ramp Trip Test: 0 to 500mA in 1mA increments. Test at 0 and 180 cycle |
Leakage Tests | Leakage Current: 0 to 30.0mA at 200 to 265V Earth Leakage Test: 240VAC Mains. Pass level 1, 2.5, 5.0 mA leakage test levels Note 1: Pass level for CLASS 1 is 5 mA; pass level for CLASS 2 is 1 mA Note 2: Leakage test may be performed if a standard CLASS 1 or CLASS 2 is not possible |
Battery | 4800 mAH, 44WH, Charge Time Around 4 Hours |