KEP SWG-12 Cable Fault Locating System
The high-voltage unit of the KEP SWG-12 Cable Fault Locating System provides with high-power up to 1100 Joules surges at 3; 6 and 12 kV ranges. At each range, the output voltage is smoothly adjustable. The rate of surge waves can be smoothly adjusted. The single manual shot option is also included. The DC output mode is provided for quick fault diagnostics. The 100 mA burn mode is available.
Digital Impulse Reflectometer (TDR) provides you with 10.4-inch bright high-contrast TFT display with touchscreen. The 800 × 600 pixels resolution makes the picture sharp. The touchscreen allows an operator navigate through the menu fast and easy. An alternative way of navigation is included. It is provided with a control knob.
Reflectometer RIF-9 integrates a multiple ways of fault prelocation. It can be used either as a standalone device in TDR mode or in a conjunction with HV‑module, working in arc reflection mode.
Reflectometer RIF-9 has USB interface. The package content includes software for PC (optional), which allows working with saved reflectograms. The firmware can be easily updated through USB interface by inserting a flash drive.
KEP SWG-12 Specifications
Parameter | Value |
GENERAL parameters | |
Supply voltage, V | 230 ± 23 |
Supply voltage frequency, Hz | 50 ± 1 |
Power consumption (max.), kVA | 2.0 |
Dimensions, mm | 1171×775×603 |
Net weight, kg | 120 |
HV-module parameters | |
TESTING MODE: | |
Output DCV range, kV | 0 – 12 |
Output DCI ranges, mA | 1; 10 |
BURNING MODE: | |
Output DCV range, kV | 0 – 12 |
Output DCI ranges, mA | 100 |
SURGE MODE: | |
Ranges, kV | 3; 6; 12 |
Surge rate, s | 3 – 15 or single shot |
Max. output energy, J | 1100 |
TDR parameters | |
Distance measurement ranges, m @ v/2 = 100 m/µs | 60; 120; 250; 500; 1000; 2000; 5000; 10000; 20000; 50000; 120000 |
Resolution, m | 0.5 @ v/2 = 100 m/µs 0.4 @ v/2 = 80 m/µs |
Sampling rate, MHz | 200 |
Gain, dB | -33 – 104 |
Output impedance (10 Ω steps), Ω | 10 – 500 |
Propagation velocity (v/2), m/µs | 50 – 150 |
Averaging reflectograms number, max. | 64 |
Time domain accuracy, % of FS | ± 0.2 |
Pulse amplitude, V | 45 |
Pulse width, ns | 10 – 100000 |
Operation modes | TDR (reflection measurement) ARC (arc-reflection) |
Control | Touchscreen and control knob |
Connectivity | RS-485, USB |
Internal data storage | 4 Gb (not less than 1000 reflectograms with data) |
Display | 10.4”, 800×600 TFT, touch-sensitive |
Operating Conditions for KEP SWG-12
The device is designed for use in outdoor conditions (moderate humidity), or under a canopy by the following conditions:
Condition | Value |
Air temperature, °С | from -10 to +40 |
Relative humidity, %, up to | 85 at +25 °С |
Atmospheric pressure, kPa (mm hg) | 84,0 – 106,7 (630 – 800) |