KEP HVT-70/50 Portable AC DC Hipot Tester
The KEP HVT-70/50 Portable AC DC Hipot Tester tests the insulation of high voltage cables and other non-liquid dielectric materials with this bundle pack from KEP Power Systems!
The system includes both a control unit and a high voltage unit, allowing the user to apply specific configurations to the material under test. By using the control panel, the user can easily easily configure and test RMS values of both AC voltage and current and filters out the effects of crest factor to reduce the chance of error.
The KEP HVT-70/50 Portable AC DC Hipot Tester comes with the ability to perform testing both automatically or manually. In automatic mode, the system will control and adjust the unit using a built-in context menu which the user can navigate through. Alternatively, specific tests can be configured to the user’s specifications and up to eight preset functions can be stored for easy repeat testing in different applications.
As the control unit is independent from the main system, the user can remain safe at all times by standing a safe distance away. Built-in auxiliary protection also automatically blocks output from the HV unit if insulating gas pressure is low, temperature is high and will block supply voltage if there is overcurrent present in the HVU supply circuit.
Technical Specifications
Parameter | Value |
Supply voltage single-phase alternating current, V | 230 ± 23 |
Frequency, Hz | 50 ± 2 |
Maximum power consumption, kVA, max | 3 |
Highest output voltage, kV: | |
– AC | 50 |
– DC | 70 |
Highest output current, mA: | |
– on AC voltage | 44 |
– on DC voltage | 14 |
Reduced voltage error, %, max: | |
– AC voltage from 2 kV to 50 kV | ± 3 |
– DC voltage from 2 kV to 70 kV | ± 3 |
Reduced current error, %, max: | |
– AC from 1,0 mA to 45,0 mA | ± 3 |
– DC from 0,5 mA to 14,5 mA | ± 3 |
Maximum current threshold on the high-voltage side, mA, max: | |
– AC voltage | 45 |
– DC voltage | 14.5 |
Control Unit dimensions, mm, max | 349 × 256 × 240 |
Control Unit Weight, kg, max | 14 |
High Voltage Unit dimensions, mm, max | 360 × 500 × 310 |
High Voltage Unit weight, kg, max | 35 |
Reviews